Preparation
1. Ensure that all systems and cells are of the same voltage and amp hour capacity.
2. Be sure that DACs are grouped per string (buying additional DACs may be necessary)
3. Connect the load cables and string voltage leads to the main positive and negative posts
of the strings in parallel
4. Connect the DACs with each battery string in the sequence of String 1 (DAC #1, #2...),
String 2 (DAC #1, #2...) and so forth. When running the discharge test, certain DACs
may need to be reassigned. (For example: DAC #1 & #2 connect to string #1. DAC #3 &
#4 connect to string #2. When running the test, DAC #3 & #4 will need to be reassigned
as DAC #1 & #2 because the 2
Function Setting
Before doing a parallel discharge test the function settings of the load bank. The SLB needs to
be configured for operation with parallel systems.
1. Select [System] under the main menu then select [Function]
2. Set "Parallel" to "2" from the default setting of "None"
3. If using DAC, set "Str Grouped" to "Yes"
Operation
After setting up the load bank for a parallel test, the discharge menu will add options for a
parallel load test. From the main menu, select [DIS test] to configure the settings for the battery
strings.
Setting up battery strings (systems)
Use the right/left arrow keys to adjust the values then press ENT to start discharging.
[Strg type]: Nominal string voltage (certain models may only have (1) nominal voltage
type selectable. i.e. a 125-100 unit does not have "48V" as an option, but can still test a
48V system)
[String]: Number of strings in parallel test. 1 SLB can do up to (5) strings
[String No.]: String number in parallel system
[Cell Type]: Nominal voltage of cells
[Cell logged]: Quantity of cells in selected string
Strg type:
String No.: 1
Cell Type: 12V
Cel logged: 04 Cell
Find Quality Products Online at:
nd
48
V
String: 2
First String
GlobalTestSupply
www.
string is independent of the 1
Strg type:
48
String: 2
String No.: 2
Cell Type: 12V
Cel logged: 04 Cell
Second String
.com
SLB-Series User Manual
string.
st
V
sales@GlobalTestSupply.com
31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents