Continued Discharge; Parallel Load Test - Eagle Eye SLB Series User Manual

Smart dc load banks
Table of Contents

Advertisement

1. Set the parameters for the first string, "String No." indicates current string
2. Change "String No." from "1" to "2" and so on to change parameters for each string
3. Press the down arrow to set parameters for the parallel strings
4. Press ENT to start the test.

Continued Discharge

It is possible to continue a discharge test that has stopped for various reasons such as cutoff
values met or manual stop. To continue a stopped discharge:
1. Enter the menu and select [Battery DIS] then select [Continued DIS]
2. If the test was stopped due to cells with low voltage, then a maximum of 6 cells can be
ignored so that the test can continue.
removed from the string. It is recommended to adjust the overall system voltage cut-off
to reflect the number of cells removed.
3. Press ENT to start the continued discharge.

Parallel Load Test

If the required discharge current is higher than the rated value of the load bank another
SLB-Series load bank of the same nominal voltage can be used in parallel to increase the
discharge current.
parallel. For example, a 48V 100A and a 48V 200A load bank can be used in parallel to
discharge up to 48V 300A.
Find Quality Products Online at:
DIS Time: 00:00:00
DIS C:0:00Ah
Ignore
Ignore Cells with Low Voltage
NOTE:
Only units with the same nominal voltage rating can be used in
GlobalTestSupply
www.
NOTE:
Ignored cells will still be discharged unless
cell:0
0
0
0
0
0
.com
SLB-Series User Manual
32
sales@GlobalTestSupply.com

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents