Technical data
Number of inputs
Number of simultaneously controllable inputs, de-
pending on the ambient temperature
Nominal voltage of the inputs
Signal voltage "0"
Signal voltage "1"
Input filter
Input current
Current consumption power contacts
Current consumption from the E-bus
Electrical isolation
Bit width in the process image
Configuration
Weight
Permissible ambient temperature range during op-
eration
Permissible ambient temperature range during
storage
Permissible relative humidity
Dimensions (W x H x D)
Mounting [} 41]
Vibration/shock resistance
EMC resistance burst/ESD
Protection class
Installation position
Approval
30
EL1104
4
4 (-25°C ... +55°C)
2 (> +55°C )
24 V
(-15% / +20%)
DC
-3 V ... 5 V (EN 61131-2, type 1/3)
11 V ... 30 V (EN 61131-2, type 1/3)
3 ms
typically 3 mA (EN 61131-2, type 1/3)
typ. 2 mA + load
typ. 90 mA
500 V (E-bus/field voltage)
4 input bits
no address setting, configuration via TwinCAT System Manager
approx. 55 g
-25°C ... +60°C
(extended temperature range)
-40°C ... +85°C
95%, no condensation
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
on 35 mm mounting rail conforms to EN 60715
according to EN 60068-2-6/EN 60068-2-27,
see also Installation instructions for terminals with increased mechanical load ca-
pacity [} 46]
conforms to EN 61000-6-2 / EN 61000-6-4
IP20
variable
CE, cULus [} 53], ATEX [} 52]
Version: 4.5
EL1114
4 (0°C ... + 55°C)
10 µs typ. (10...50 µs)
0°C ... + 55°C
-25°C ... + 85°C
CE, cULus [} 53], ATEX [} 51]
EL10xx, EL11xx