El1084, El1088, El1094, El1098 - Technical Data - Beckhoff EL10 Series Documentation

Digital input terminals
Table of Contents

Advertisement

Product overview
2.4.3

EL1084, EL1088, EL1094, EL1098 - Technical data

Technical data
Number of inputs
Nominal voltage of the inputs
Signal voltage "0"
Signal voltage "1"
Input filter
Input current
Current consumption power contacts
Current consumption via E-bus
Electrical isolation
Bit width in the process image
Configuration
Weight
Permissible ambient temperature
range during operation
Permissible ambient temperature
range during storage
Permissible relative humidity
Dimensions (W x H x D)
Mounting [} 41]
Vibration/shock resistance
EMC resistance burst/ESD
Protection class
Installation position
Approval
28
EL1084
EL1088
4
8
24 V
(-15% / +20%)
DC
18 V ... 30 V
0 V ... 7 V
3 ms
3 ms
typ. 3 mA
typ. 20 mA
typ. 25 mA
typ. 90 mA
500 V (E-bus/field voltage)
4 input bits
8 input bits
no address setting, configuration via TwinCAT System Manager
approx. 55 g
0°C ... + 55°C
0°C ... + 55°C
(aligned in horizontal
installation position)
0°C ... + 45°C
(all other installation
positions,
see Note [} 44])
-25°C ... + 85°C
95%, no condensation
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
on 35 mm mounting rail conforms to EN 60715
according to EN 60068-2-6/EN 60068-2-27,
see also Installation instructions for terminals with increased mechanical load capacity
[} 46]
conforms to EN 61000-6-2 / EN 61000-6-4
IP 20
variable
see note [} 44]
CE, cULus [} 53], ATEX [} 51]
Version: 4.5
EL1094
EL1098
4
8
10 µs
10 µs
typ. 20 mA
typ. 25 mA
4 input bits
8 input bits
0°C ... + 55°C
0°C ... + 55°C
(aligned in horizontal
installation position)
0°C ... + 45°C
(all other installation
positions,
see Note [} 44])
variable
see note [} 44]
EL10xx, EL11xx

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents