El1012, El1014, El1018 - Technical Data - Beckhoff EL10 Series Documentation

Digital input terminals
Table of Contents

Advertisement

Product overview
2.2.4

EL1012, EL1014, EL1018 - Technical data

Technical data
Number of imputs
Number of simultaneously controllable in-
puts, depending on the ambient tempera-
ture
Nominal voltage of the inputs
Signal voltage "0"
Signal voltage "1"
Input filter
Input current
Current consumption power contacts
Current consumption via E-bus
Electrical isolation
Bit width in the process image
Configuration
Weight
Permissible ambient temperature range
during operation
Permissible ambient temperature range
during storage
Permissible relative humidity
Dimensions (W x H x D)
Mounting [} 41]
Vibration/shock resistance
EMC resistance burst/ESD
Protection class
Installation position
Approval
22
EL1012
2
2 (> +55°C )
24 V
(-15% / +20%)
DC
-3 V ...5 V (EN 61131-2, type 1/3)
11 V ... 30 V (EN 61131-2, type 1/3)
10 µs typ. (10...50 µs)
typically 3 mA (EN 61131-2, type 1/3)
typ. 2 mA + load
typ. 90 mA
500 V (E-bus/field voltage)
2 input bits
no address setting, configuration via TwinCAT System Manager
approx. 55 g
-25°C ... +60°C
(extended temperature range)
-40°C ... +85°C
95%, no condensation
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
on 35 mm mounting rail conforms to EN 60715
according to EN 60068-2-6/EN 60068-2-27,
see also Installation instructions for terminals with increased mechanical load capacity
[} 46]
conforms to EN 61000-6-2 / EN 61000-6-4
IP20
variable
CE, cULus [} 53], ATEX [} 52]
Version: 4.5
EL1014
EL1018
4
8
4 (-25°C ... +55°C)
8 (-25°C ... +55°C)
2 (> +55°C )
4 (> +55°C )
(aligned in horizontal installa-
tion position) [} 44]
typ. 90 mA
typ. 90 mA
4 input bits
8 input bits
-25°C ... +60°C
(extended temperature range,
aligned in horizontal installa-
tion position [} 44])
-25°C ... +45°C
(all other installation positions
[} 44])
see note [} 44]
EL10xx, EL11xx

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents