El1002, El1004-00X0, El1008 - Technical Data - Beckhoff EL10 Series Documentation

Digital input terminals
Table of Contents

Advertisement

Product overview
2.1.4

EL1002, EL1004-00x0, EL1008 - Technical data

Technical data
Number of inputs
Number of simultaneously controllable in-
puts, depending on the ambient tempera-
ture
Nominal voltage of the inputs
Signal voltage "0"
Signal voltage "1"
Input filter
Input current
Current consumption power contacts
Current consumption via E-bus
Electrical isolation
Bit width in the process image
Configuration
Weight
Permissible ambient temperature range
during operation
Permissible ambient temperature range
during storage
Permissible relative humidity
Dimensions (W x H x D)
Mounting [} 41]
Vibration/shock resistance
EMC resistance burst/ESD
Protection class
Installation position
Approval
18
EL1002
EL1004
2
4
2 (> +55°C )
4 (-25°C ... +55°C)
2 (> +55°C )
24 V
(-15% / +20%)
DC
-3 V ... 5 V (EN 61131-2, type 1/3)
11 V ... 30 V (EN 61131-2, type 1/3)
3 ms
typically 3 mA (EN 61131-2, type 1/3)
typ. 2 mA + load
typ. 90 mA
500 V (E-bus/field voltage)
2 input bits
4 input bits
no address setting, configuration via TwinCAT System Manager
approx. 55 g
-25°C ... +60°C
(extended temperature range)
-40°C ... +85°C
95%, no condensation
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
on 35 mm mounting rail conforms to EN 60715
according to EN 60068-2-6/EN 60068-2-27,
see also Installation instructions for termi-
nals with increased mechanical load capac-
ity [} 46]
conforms to EN 61000-6-2 / EN 61000-6-4
IP20
variable
CE, cULus [} 53], ATEX [} 52], IECEx
Version: 4.5
EL1004-0020
EL1008
8
8 (-25°C ... +55°C)
4 (> +55°C )
(aligned in horizontal
installation position)
[} 44]
2500 V functional iso-
500 V (E-bus/field volt-
lation (test voltage E-
age)
bus / field voltage,
production test).
8 input bits
0°C ... +55°C
-25°C ... +60°C
(extended temperature
range,
aligned in horizontal in-
stallation position
[} 44])
-25°C ... +45°C
(all other installation
positions [} 44])
-25°C ... +85°C
-40°C ... +85°C
according to EN
according to EN
60068-2-6/EN
60068-2-6/EN
60068-2-27
60068-2-27,
see also Installation in-
structions for terminals
with increased mechani-
cal load capacity [} 46]
see note [} 44]
CE, cULus [} 53]
CE, cULus [} 53], ATEX
[} 52], IECEx
EL10xx, EL11xx