El1024, El1034 - Technical Data; Fig. 16 El1024 - Beckhoff EL10 Series Documentation

Digital input terminals
Table of Contents

Advertisement

EL1034 - Connection
Terminal point
Description
Name
No.
Input 1
1
Input 1
GND 1
2
Ground (GND) 1
GND 3
3
Ground (GND) 3
Input 3
4
Input 3
Input 2
5
Input 2
GND 2
6
Ground (GND) 2
GND 4
7
Ground (GND) 4
Input 4
8
Input 4
2.3.3

EL1024, EL1034 - Technical data

Technical data
Number of inputs
Nominal voltage of the inputs
Signal voltage "0"
Signal voltage "1"
Input filter
Input current
Current consumption power contacts
Current consumption via E-bus
Electrical isolation
Bit width in the process image
Configuration
Weight
Permissible ambient temperature range during op-
eration
Permissible ambient temperature range during
storage
Permissible relative humidity
Dimensions (W x H x D)
Mounting [} 41]
Vibration/shock resistance
EMC resistance burst/ESD
Protection class
Installation position
Approval
EL10xx, EL11xx
EL1024
4
24 V
(-15% / +20%)
DC
-3 V ... 5 V (EN 61131-2, type 2)
11 V ... 30 V (EN 61131-2, type 2)
3 ms
typically 6 mA (EN 61131-2, type 2)
typ. 30 mA + load
typ. 90 mA
500 V (E-bus/field voltage)
4 input bits
no address setting, configuration via TwinCAT System Manager
approx. 55 g
0°C ... + 55°C
-25°C ... + 85°C
95%, no condensation
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
on 35 mm mounting rail conforms to EN 60715
according to EN 60068-2-6/EN 60068-2-27,
see also Installation instructions for terminals with increased mechanical load ca-
pacity [} 46]
conforms to EN 61000-6-2 / EN 61000-6-4
IP20
variable
CE, cULus [} 53], ATEX [} 51]
Version: 4.5
Product overview
EL1034
4 (potential-free)
-3 V ... 5 V (EN 61131-2, type 1)
15 V ... 30 V (EN 61131-2, type 1)
10 µs
typically 3 mA (EN 61131-2, type 1)
-
25