Grounding the Access Point (all models)
Figure 3-11
1 - 6
Grounding the Access Point (all models)
The access point must be grounded before connecting power.
This equipment must be externally grounded using a customer-supplied ground wire before power is
Warning
applied. Contact the appropriate electrical inspection authority or an electrician if you are uncertain
that suitable grounding is available. Statement 366
Installation of the equipment must comply with local and national electrical codes. Statement 1074
Warning
In all outdoor installations and when powering the access point with AC power, you must follow these
instructions to properly ground the case:
Step 1
If using insulated 6-AWG copper ground wire, strip the insulation as required for the grounding lug.
Step 2
Use the appropriate crimping tool to crimp the bare 6-AWG copper ground wire to the supplied
grounding lug (Panduit PLCD6-10A-L).
Note
Cisco Aironet 1552 Series for Hazardous Locations Installation Guide
3-60
Hinged Cover Bolt Tightening Sequence
5
Tighten the bolts in the numeric order shown, starting with 1.
The grounding lug and hardware used must comply with local and national electrical codes.