2Nd Level Programming - BFT PERSEO-CBE Installation And User Manual

Table of Contents

Advertisement

·
: Close con guration
:
-
Close-when-released input
The bollard closes automatically only when the vehicle has completely passed by the photocell or magnetic detector (the recom-
mended accessories for this purpose). Connect the N.O. contact of the detector or photocell to the close input terminals.
If the vehicle is on the detector or in front of the photocell it does not cause immediate closing but the control board will wait for
the signal to be released (i.e. vehicle moved).
-
: The close command acts as close-when-released and safety function.
When closing, a close command stops the automation. When close input becomes inactive the bollard resumes closing.
·
: Preset
- To con gure the parameters for installation type A, B, C and D; set the corresponding value and exit the menu. See chapter 13 for
details on installation types.
·
: Default
- To restore the parameters to the factory default values, set the "DF" to 1 or 2, then exit the menu. if
"Com" settings is are kept.
Warning: The "default" operation sets all parameters to the factory default values, including the Preset values and the bollard type.
The following table gives the 2nd level functions and the adjustable parameters.
= DEFAULT value set in factory.
Par
Function
Request for maintenance
Programming maintenance
cycles in thousands
Programming maintenance
cycles in millions
Output 4, Output 5
Closing limit switch presence
ECD present (for SD version
and XPASS B 1200C)
TERMON
UPS
Control unit
8.3
PROGRAMMING
2nd LEVEL
= parameter value set during installation: should be lled if DE-
: disabled
: active on the con gured outputs
: as in
plus lights ash twice
.
.
: scheduled maintenance required
: photocell triggering
: obstacle detection (for hydraulic bollard only)
: PDM input active
: bollard fully up (close position)
: bollard fully down (open position)
: STOP input active
: warning ash
: START input active
: OPEN input active
: power failure (the output is activated at switch-on)
: assistance required
: CLOSE input active
: UPS
: second radio channel active
: buzzer (for Totem)
: not present
: present
: not present
: present
: heating level (
= min;
: disabled
: enabled, opens automatically during mains failure
: enabled, closes automatically during mains failure
WARNING:THIS SELECTION MAY BE DANGEROUS
- 31 -
FAULT value is modi ed.
Settable data
= max)
EN
=
the communication
.
see
note

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents