2. Commissioning
Inserting modules
2−48
Example: When using the bus node from the previous
example (CPX−FB33 with Rev 14) in the operating mode
remote I/O with diagnostics mode status bits but
without the additional function Fast Start−up", choose
the bus node module FB33 with mode identification
Status (from the field device group Bus nodes"
underneath the CPX station symbol): FB33 PNIO module
[Status] ( 2 in Tab. 2/4).
First pull the bus node onto the first line of the
·
configuration table (Slot" 1, 2 in Tab. 2/4, also
designated as function card position 1 or card slot 1).
Check the setting of the DIL switches for operating
·
mode and diagnostics mode (see section 1.4.2):
Ensure that the setting for operating mode and
diagnostics mode selected through DIL switches at
the bus node matches the function of the catalogue
element.
Then pull the first (left) module of your CPX terminal
·
from the field device group onto line 2 in the
configuration table.
Drag the next module to the respective next free row
·
of the configuration table.
Alternatively, you can also double click on the catalogue
element: Select the next free row in the rack rail window
before you make the double click.
Festo P.BE−CPX−PN IO−EN en 1008b