Festo CPX Series Manual page 126

Bus node, network protocol profinet io
Hide thumbs Also See for CPX Series:
Table of Contents

Advertisement

3. Diagnosis
M parametrisation modified or forcing active (modify)
LED (yellow)
Procedure
ON
OFF
LED is off
ON
OFF
LED lights up
ON
OFF
LED flashes
1
The display of the Force function (LED flashes) has priority over the display of the setting for the
system start (LED lights).
Tab. 3/7:
CPX system/terminal status (part 3) LED M
3−10
Installation
System start with
factory settings (default
parametrisation) and
current CPX expansion
External parametrisation
possible (default)
System start with saved
parametrisation and
saved CPX expansion
Parameters and CPX
expansion are
retentively saved;
external parametrisation
1)
is blocked
1)
Forcing active
Meaning/error handling
None
Caution when replacing a CPX terminal
with saved parametrisation
(LED M lights up):
In case of servicing, such as with
replacement of the CPX terminal,
parametrisation is not created
automatically by the PLC or the
higher−order system. In this case,
check which settings are required
before replacement and make these
settings if necessary.
The Force function has been activated
(Force mode; Function No. 4402, see
CPX System Manual P.BE−CPX−SYS...).
Festo P.BE−CPX−PN IO−EN en 1008b