Parameter setting
Parameter setting using the keypad
2.2.5

Parameter set transfer

(possible only when the controller is inhibited)
Warning!
During parameter set transfer, the control terminals of the 9300 servo can have undefined states!
Therefore the plugs X5 and X6 must be removed before transfer. Thus it is ensured that the controller
is inhibited and all control terminals have the defined state "LOW".
You can transfer complete parameter sets from one controller to another using the keypad. When
copying from the controller to the keypad all parameter sets will be copied and saved in the keypad.
1. Plug keypad on controller 1.
2. Inhibit controller with X5/28 = LOW.
3. Save the last modifications in the corresponding parameter set under C0003.
4. Change from the menus to the code level using the arrow keys. "Code" is displayed.
5. Select C0810/1 using
6. Change to the parameter level using PRG."Para" is displayed.
7. Select parameter 11.
8. Press SHIFT + PRG. RDY is no longer displayed. BUSY is displayed.
All parameter sets are copied to the keypad. Copying is completed when BUSY is no longer
displayed (after approx. one minute).
Stop!
Remove keypad only when BUSY is off. Otherwise, TRIP "PRX" will be activated.
9. Enable controller with X5/28 = HIGH.
10.Plug the keypad on controller 2.
11.Inhibit controller 2 with X5/28 = LOW.
12.Change from the menus to the code level using the arrow keys. "Code" is displayed.
13.Select C0810/1 using
14.Change to the parameter level using PRG."Para" is displayed.
15.Select parameter 20 to copy all parameter sets from the keypad to controller 2 and to save
them.
16.Press SHIFT + PRG. RDY is no longer displayed. BUSY is displayed.
All parameter sets are copied to and saved in controller 2. Copying and saving are completed
when BUSY is no longer indicated.
17.Enable controller with X5/28 = HIGH.
Tip!
You can also copy individual parameter sets from the keypad to controller 2:
For this, use the 15. parameters 11, 12, 14 or 14 instead of parameter 20 in step 15, to copy
the parameter sets 1, 2, 3 or 4 to controller 2.
You have to save the copied parameter sets if you do not want to loose the modifications
after mains disconnection.