Parameter setting
Parameter setting using the keypad
2.2.4
Load parameter set
(possible only when the controller is inhibited)
Warning!
•
When a new parameter set is loaded, the controller is reinitialised and acts as if it was
connected to the mains:
– System configurations and terminal assignments may be changed. Ensure, that your wiring
and drive configuration correspond to the settings of the parameter set.
•
Only use terminal X5/28 as a source for controller inhibit! Otherwise the drive may start
accidentally when changing to another parameter set.
Tip!
The RDY message is not displayed while the parameter set is loaded since the controller cannot
be operated then.
Mains connection
The controller automatically loads parameter set 1.
Via keypad
1. X5/28 = LOW
2. Select C0810/1 using
3. Change to the parameter level using PRG.
4. Select C0810/1 using
5. Press SHIFT + PRG.
"OK" is displayed. When "OK" is no longer displayed, the loading is completed.
6. Enable controller with X5/28 = HIGH.
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - e.mail: info@ctiautomation.net
or
select C0002.
Y
B
or
select the desired parameter set.
Y
B