Parameter setting
Parameter setting using the keypad
2.2.2
Change of parameters
Tip!
Changed parameter sets must be saved, if you do not want to loose the modifications after mains
disconnection (see chapter 2.2.3).
Basic procedure
1. Change to the code level from the menus using the arrow keys
"Code" is displayed.
2. Select C0810/1 using
3. Change to the parameter level using PRG."Para" is displayed.
4. Select C0810/1 using
changed.
5. Select C0810/1 using
6. Repeat 4. and 5. to change other numbers, if ncessary.
7. Accept parameters. The way the controller accepts the modified parameters is shown in the
LCD display in front of the parameter:
Display in front of the parameter
SH+PRG
SH+PRG
8. Press PRG twice to go to the code level. "Code" is displayed.
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - e.mail: info@ctiautomation.net
or
select code or subcode.
Y
B
or
move the cursor (small, black bar) under the number to be
A
"
or
change number.
Y
B
Controller uses the new value
Immediately during the change
after pressing SH+PRG. Confirmation: ok in the display
Press STOP to inhibit the controller.
Press SHIFT + PRG. Confirmation: ok in the display
Press RUN to enable the controller
,
,
or
to the code level.
Y
B
A
"