External Layouts/Dimensions; Dimensional Data; Electrical Conduit Landing Plate Data - Toshiba 4400 Series Installation And Operation Manual

Battery cabinets
Table of Contents

Advertisement

10

External Layouts/Dimensions

10.1

Dimensional Data

Unit
440B 15-30kVA
440B 50-100kVA
10.2

Electrical Conduit Landing Plate Data

440B 15-30kVA
440B 50-100kVA
Run the power cabling in a separate conduit from the control wiring.
The 440B 15-30kVA Battery cabinet has pre configured knockouts on the bottom of the expansion band: the smaller single
knockout is for the instrumentation cabling conduit, and the two larger knockouts on th right side are for the power cabling
conduits.
If running top-entry cabling to the 440B 15-30kVA Battery Cabinet the small conduit landing plate on the left should be used for
instrumentation, and drill the power cables conduit holes on the right side of the top expansion band.
4400 Series UPS Battery Cabinet Installation and Operation Manual – 69445-005
Table 10.1 - External Dimensions
EXTERNAL DIMENSIONS
Width
20.12 in. (511 mm)
32.1 in. (816 mm)
Table 10.2 - Conduit Access Ports
CABLE ACCESS OPENING SIZES IN 440B
Left/Right Side
2.6 in. x 14.1 in.
L Side - 1" x 3" Conduit landing plate.
(67 mm x 359 mm)
R Side - 3.5 in.
3.85 in. x 21.13 in.
(98 mm x 536 mm)
Depth
37.4 in. (950 mm)
37.2 in. (944 mm)
Top
4.4 in. x 27.7 in.
(111 mm x 703 mm)
Height
65.06 in. (1653 mm)
73.6 in. (1868 mm)
Bottom
L Side: 1" Trade-size Knock Out
R Side: 2 x 1.25" Knock-outs
4.4 in. x 27.7 in.
(111 mm x 703 mm)
29