TABLE 9.1 - UPS STORAGE/OPERATING ENVIRONMENT STANDARDS
Item
Storage Location
Ambient Temperature
Relative Humidity
Altitude
Dust
Flammable Gas
5.3

Operating Precautions

Initial startup/commissioning of the
1) The
battery cabinet
read. Follow Lockout/Tag Out procedures.
2) The voltage of the input power source must be within the rated input voltage range. The
input frequency range must be within the rated input frequency range.
3) The
battery cabinet
than the rated output of the UPS.
4) If using the
or with motors that require a long starting time, call Toshiba support for guidance in over
sizing the UPS for locked-rotor current.
5) DO NOT insert metal objects or combustible materials in the ventilation slots of the
cabinet.
6) DO NOT place, hang, or paste any objects on the exterior surfaces of the
7) DO NOT attempt to disassemble, modify, or repair the
sales representative for repair information.
8) Turn the power on only after installing ALL of the covers.
9) DO NOT remove any covers of the
10
Environment standard
Indoors
Minimum storage temperature: 32 °F (0 °C)
Maximum storage temperature: 104 °F (40 °C)
The relative humidity must be between 30 and 90% and without
condensation due to temperature changes.
This equipment is rated for installations up to 3240 ft. (1000 m)
above sea level. Consult with the factory to determine the derating
factor for installations above 3240 ft. (1000 m).
Dust must not exceed normal atmospheric levels and must not
include conductive/corrosive particles, silicone or oils.
No flammable and/or explosive gas.
Hydrogen sulfide (H
Sulfurous acid gas (SO
Chlorine gas (Cl
Ammonia gas (NH
Nitrous acid gas (NO
Nitrous oxides (NOx)
Ozone (O
)
3
Hydrochloric acid mist (HCl) Less than or equal to 0.1 mg/m
battery cabinet
should not be powered up until the entire operation manual has been
should not be used with a load that has a rated input that is greater
battery cabinet
to provide power to motors that require high starting current
battery cabinet
4400 Series UPS Battery Cabinet Installation and Operation Manual – 69445-005
S)
Less than or equal to 0.0001 PPM
2
)
Less than or equal to 0.05 PPM
2
)
Less than or equal to 0.002 PPM
2
)
Less than or equal to 0.1 PPM
3
)
Less than or equal to 0.02 PPM
2
Less than or equal to 0.02 PPM
Less than or equal to 0.002 PPM
should be performed by factory authorized personnel.
battery
when power is on.
3
battery
battery
cabinet.
cabinet. Call your Toshiba