9

Storage/Operating Environment

Observe the following when storing the UPS.
Store UPS indoors.
Maximum storage time for the UPS between powered operation cycles is three years. If the UPS
has been stored for a period exceeding 36 months, contact your factory authorized represnetative
of guidance in starting the unit.
Temperature fluctuations should be minimized.
The optimal storage temperature range is 68 – 77 °F (20 – 25° C).
A maximum temperature range of 32 – 104 °F (0 – 40 °C) should be observed.
The optimal relative humidity at the storage location should be between 50 – 60%.
Humidity must not exceed 90%.
Avoid locations where UPS may be exposed to corrosive gas.
Avoid locations with dirt and/or dust.
TABLE 9.1 - UPS STORAGE/OPERATING ENVIRONMENT STANDARDS
Item
Environment standard
Storage Location
Indoors
Minimum storage temperature: 32 °F (0 °C)
Ambient Temperature
Maximum storage temperature: 104 °F (40 °C)
The relative humidity must be between 30 and 90% and without condensation
Relative Humidity
due to temperature changes.
This equipment is rated for installations up to 3240 ft. (1000m) above
Altitude
sea level. Consult with the factory to determine the derating factor for
installations above 3240 ft. (1000m).
Dust must not exceed normal atmospheric levels and must not include
Dust
conductive particles, silicone or oils.
No flammable and/or explosive gas.
Hydrogen sulfide (H
Sulfurous acid gas (SO
Chlorine gas (Cl
Flammable Gas
Ammonia gas (NH
Nitrous acid gas (NO
Nitrous oxides (NOx)
Ozone (O
Hydrochloric acid mist (HCl)
9.1

Operating Precautions

Initial startup/comisioning of the UPS should be performed by factory authorized personnel.
1) The UPS should not be powered up until the entire operation manual has been read.
2) The voltage of the input power source must be within the rated input voltage range. The
G8000 Series Installation and Operation Manual
S)
Less than or equal to 0.0001 PPM
2
)
Less than or equal to 0.05 PPM
2
)
Less than or equal to 0.002 PPM
2
)
Less than or equal to 0.1 PPM
3
)
Less than or equal to 0.02 PPM
2
Less than or equal to 0.02 PPM
)
Less than or equal to 0.002 PPM
3
Less than or equal to 0.1 mg/m
3