1. Installation
1.3.3 Connecting the field bus
Bus connection
Socket
Pin
1
2
3
4
5
6
7
8
9
Housing
1)
Repeater control signal CNTR-P is designed as a TTL signal.
Tab. 1/6:
Pin assignment of the field bus interface of the CPX field bus node
1-20
Please note
If the CPX terminal is fitted onto the moving part of a ma-
chine, the field bus cable on the moving part must be pro-
vided with strain relief. Please observe also the relevant
regulations in EN 60204 part 1.
There is a 9-pin sub-D socket on the field bus node for con-
necting the CPX terminal to the field bus. This connection
serves for the incoming and continuing field bus cable. You
can connect the CPX terminal with the sub-D plug from Festo
(part nos. 18529).
Festo sub-D plug
PROFIBUS-DP
(IP65)
-
Screening/shield
-
n.c.
B
RxD/TxD-P
-
CNTR-P
-
DGND
-
VP
-
n.c.
A
RxD/TxD-N
-
n.c.
Cable clip
Screening/shield
Designation
Connection to functional earth
not connected
Receive/send data P
1)
Repeater control signal
Data reference potential (M5V)
Power supply positive (P5V)
not connected
Receive/send data N
not connected
Connection to functional earth
Festo P.BE-CPX-FB13-EN en 0112NH