Toshiba V Series User Manual page 57

Integrated controller, loop controller
Hide thumbs Also See for V Series:
Table of Contents

Advertisement

When this switch is pressed at the same time as the manual operation switches or SV
switch, the change rate is set to FAST. This switch, used alone, changes the mode from
SELECT to NORMAL or vice versa.
The SELECT and NORMAL modes allow selection of two or more functions with the
single switch (FAST/SEL) as follows.
SELECT mode
• Switching digital indication items (PV/SV/MV)
• Switching display loops (in multiloop display)
• Alarm check
NORMAL mode
• PH/PL indication (SV LED bar graph)
• Alarm check
In SELECT mode, the SELECT indicator LED located next to the FAST/SEL switch
remains lit.
Press the FAST/SEL switch for less than 1 second to switch the mode from SELECT to
NORMAL or vice versa.
The functions are executed in these modes as shown in Table 1-35
FAST/SEL switch
Press for less than 1 second Changed to NORMAL mode
Press for longer than 1
second
6F8C1005
Table 1-35 Operation
SELECT mode
Changed to NORMAL mode
1.7 Software Functions
NORMAL mode
Changed to SELECT mode
PH/PL indication function is
executed. After 1 second, PH/
PL is displayed while the switch
is being pressed. At the same
time, alarm check is made.
NORMAL mode remains.
1