Replacing an NT7D10 PDU with an NT7D67CB PDU
Installing equipment
DANGER
The NT7D67CB PDU is much heavier than the
NT7D10 PDU.
Note: The conduit attachment plate provided in the NT7D0902 Rear
Mount Conduit Kit must be installed as a safety cover and to restrain
wiring to the terminal block.
1
Drill two .234-in. screw holes in the rear of the pedestal (see Figure 41
on page 237). The holes will be used to install the conduit attachment
plate.
Figure 41
Dimensions for drilling holes on the pedestal
Drill .234 in.
diameter through
(two places)
2
Place the NT7D67CB PDU next to the pedestal.
Figure 42 on page 238 shows the PDU (labeled FLTR/PWR DIST UNIT ASSY
on the equipment) and the NT7D10CA System Monitor/Power Supply
Assembly (labeled XSM/PWR SUPPLY ASSY on the equipment).
Note: The NT7D09CA Pedestal has a brace that supports a leveling
bracket on the rear of the PDU. There is no room for the leveling
bracket in the NT7D09AA Pedestal, so the bracket must be removed
before the PDU is installed.
9.13 in.
.75 in.
Page 237 of 250
1.0 in.
553-5489
Hardware Replacement