553-3001-520 Standard 17.00 January 2002
Replacing equipment
Figure 30
Connections at the field wiring terminal
J3
c.
Disconnect the power plug (J1) and system monitor ribbon cable
to the module.
Note: To disconnect the power plug, you must press a latch trip on the
front and rear of the plug. You may need to use a screwdriver blade
against the latch trip on the front of the plug.
7
Remove the six screws that position the PDU. Carefully pull the unit
straight forward out of the pedestal.
Installing equipment
1
Set the main circuit breaker on the replacement PDU to OFF (down).
2
Position the replacement PDU and gently push it into the pedestal.
Note: Be sure you push the unit straight back, so the connector on the
rear will seat properly with the blower unit connector. It may be easier
to position the PDU if you temporarily pull the blower unit out several
inches.
3
Reconnect cables to module 0:
a.
Attach power plug J1 and the system monitor cable.
b.
Replace the I/O safety panel.
c.
Replace the rear cover.
4
Insert the system monitor. Tighten the screws on the card. Reconnect
cables to the system monitor faceplate.
J5
J6
J4
PDU
LRTN
GND
L2
L1
To LRE
553-3086