Nortel Meridian 1 Hardware Replacement Manual page 154

Table of Contents

Advertisement

Page 154 of 250
553-3001-520 Standard 17.00 January 2002
Replacing equipment
Figure 11
Cabling between the PDU and the field wiring terminal block
Blower
unit
PDU
position in
the pedestal
c.
Reconnect all wiring to the field wiring terminal block, including
any jumpers that might have been present on the terminal block
that was removed.
d.
Reconnect the frame ground wire from the frame ground bolt
inside the pedestal to the field wiring terminal block.
e.
Replace the cover over the field wiring terminal block.
2
Gently push the PDU into the pedestal. Replace the screws on the
PDU.
Note: Be sure you push the unit straight back so the connector on the
rear will seat properly with the connector for the blower unit.
3
Reconnect cables from module 0 to the PDU:
a.
Attach power plug J1 and the system monitor cable.
b.
Replace the I/O safety panel on the module.
c.
Replace the rear cover on the module.
View looking down at the pedestal
PDU
pulled out of
the pedestal
(located beneath
Pedestal rear
Field wiring
terminal block
the PDU)
553-5487