EDGE INPUT (28-29):
•
The EDGE input may be configured as a monitored ANALOG input,
or DIGITAL (NC or NO) input.
•
The EDGE sensor input is intended for ANSI/UL 325 listed gate
edge sensors to protect against entrapment and hazardous pinch
points along the moving edge of the closing gate.
•
Additional options are available to declare if the edge is protecting
the open or close direction, and the input must measure 8.2K - 10K
Ohms.
•
When the input is activated it stops the gate regardless of direction
of travel, momentarily reverses it then stops.
PIN 28 = EDGE
PIN 29 = GND
EXIT INPUT (30-31):
•
The EXIT sensor input is provided to activate to open the gate, or re-open a closing gate, upon sensing an
exiting vehicle.
•
This is a dry contact input for a vehicle exit sensor.
•
Shorting the EXIT input to GND opens gate from the closed position and holds gate open with maintained
input or reverses gate if closing.
PIN 30 = EXIT
PIN 31 = GND
FIRE INPUT (32-33):
•
Dry contact input for a fire department control switch.
•
Shorting the Fire input (32) to GND opens the gate and holds the gate open
until control switch is deactivated.
•
Auto-close is disabled when this input is activated. Also clears hard shutdown.
PIN 32 = FIRE
PIN 33 = GND
www.ApolloGateOpeners.com | (800) 878-7829 | Sales@ApolloGateOpeners.com
7251 / 7351 Slide Gate Operator
INSTALLATION AND PROGRAMMING MANUAL
EXIT DEVICE
EDGE SENSOR AND
EXIT DEVICE WIRING
(EXAMPLE)
FIRE DEPT. INPUT
WIRING (EXAMPLE)
65