Interfaces
SafetyBUS p interface ("SafetyBUS p 0" and "SafetyBUS p 1")
Connection to SafetyBUS p is via a male 9-pin D-Sub connector. Detailed
information on SafetyBUS p can be found in the SafetyBUS p manual.
Male D-Sub connector
9-pin
Fig. 8-6: Configuration of the SafetyBUS p interface

Interfaces for standard bus connections

The standard bus interfaces are described in separate operating manuals.
The necessary operating manuals are supplied with each programmable
safety system in the PSS SB2 3006-3 series, depending on the unit type.
8-8
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
6
9
1: n.c.
2: CAN_L
(brown)
3: CAN_GND (white)
4: n.c.
5: CAN_SHLD
6: n.c.
7: CAN_H
(green)
8: Supply voltage for fibre-optic couplers
from Pilz
9: n.c.
n.c. = not connected