Example: Dual-Channel, Failsafe Input Device, With Test Pulses - Pilz PSS Series Operating Manual

Safety systems; units with two safetybus p interfaces
Hide thumbs Also See for PSS Series:
Table of Contents

Advertisement

Wiring the Inputs and Test Pulse Outputs

Example: Dual-channel, failsafe input device, with test pulses

Features:
• This type of connection is mainly used for signal inputs with infrequent
operation.
• The test pulse must be allocated to the input via the configurator on the
programming device (see Programming Manual for the PSS-range).
• On input devices with identical channels, each channel should be given a
separate test pulse, where possible. This will ensure that all short circuits
are detected, with the exception of short circuits which short out the input
device (cable from the test pulse to the input device and cable from the
input device to the input).
• If the input device has only one test pulse, a short circuit between the
cables from the input device to the inputs will not be detected. In this
case the unit should be suitably wired to avoid the risk of this type of
short circuit. If diverse input devices are used, this type of error will be
detected.
24 V DC
Continued overleaf ...
7-8
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
X1
0 V
T 0
T 1
I 0.0
I 0.1
I 0.2
I 0.3
I 0.4
I 0.5
L+
L-
Dual-channel input device
with diverse channels
Operating Manual: PSS SB 3006-3 Series

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pss sb2 3006-3 cn-aPss sb2 3006-3 dn-sPss sb 3006-3 seriesPss sb2 3006-3 eth-2Pss sb2 3006-3 eth-2 dp-sPss sb2 3006-3 eth-2 ibs-s ... Show all