PSEN sl1.0p 3.1/4.1/4.2
Connection to Pilz evaluation devices
The safety switch PSEN sl1.0p 3.1/4.1/4.2 can be connected to Pilz evaluation devices, for
example. Make sure that an evaluation device is selected that can evaluate OSSD signals
through two channels.
Suitable Pilz evaluation devices are, for example:
}
PNOZelog for safety gate monitoring
}
PNOZpower for safety gate monitoring
}
PNOZsigma for safety gate monitoring
}
PNOZ X for safety gate monitoring
}
PNOZmulti for safety gate monitoring
Configure the switch in the PNOZmulti Configurator with switch type 3.
}
PSS for safety gate monitoring with standard function block SB064, SB066 or
FS_Safety Gate
The correct connection to the respective evaluation device is described in the instructions
for the evaluation device. Make sure that the connection is made in accordance with the
specifications in the instructions for the selected evaluation device.
The connections to two evaluation devices are shown on the following pages, by way of ex
ample:
}
PNOZ s3 and
}
PNOZmulti
Connection example PNOZ s3
Operating Manual PSEN sl1.0p 3.1/4.1/4.2
1003389EN02
CAUTION!
When several units are connected in series, the max. solenoid current in
creases in direct proportion to the number of interconnected safety switches
(see Technical details [
PNOZ s3
A1
A2
S12
S22
26], Max. inrush current impulse A1).
PSENslock
A1
2
7
A2
5
Y32
8
S31
6
S11
1
S21
3
12
4
22
15