Caution
Entry - - - -
Boiler off
Pump on (burner off)
Stage 1 controlled
108/232
Building Technologies
HVAC Products
T
T
T
T
7.7
Test mode and commissioning aids
During commissioning and for test purposes, boiler and burner can be put into various
operating states via the service level.
Main menu > Boiler ... > Test mode
Operating line
Preselection test mode
Boil setp test mode
Modulation value test mode
Actual value boiler temperature
Test mode is not automatically ended (no monitoring of time-out!).
Only authorized personnel should override the inputs – and for a limited period of time
only!
During the test mode, fault status message "Boiler test operation active" appears. This
display is maintained until "Test operation" is reset to "----". This ensures that the plant
is not quit before test operation is ended.
In position "----", the boiler is released and receives its presettings from the boiler
sequence manager.
The boiler is shut down, that is, burner and pumps are switched off.
The boiler is released. The aggregates (shutoff valve, maintained boiler return tempera-
ture with mixing valve, boiler pump) are active, but the burner is still switched off.
The boiler is released and the burner with its stage 1 or basic stage maintains the
adjusted test mode setpoint.
Boiler Sequence Controller RMK770
7 Boiler control
T
T
T
T
T
Range
Auto / Boiler off /
Stage 1 controlled /
Stage 1+ 2 controlled /
Modulating fixed
10...95 °C
0...100%
Measured value
T
Factory setting
Auto
60 °C
0%
CE1P3132en
23.04.2009