Settings
Fault status messages
Building Technologies
HVAC Products
11.3.7 Assignment of texts
Each meter can be assigned specific text. This text appears on the operating pages in
the form of menu text and datapoint text.
Main menu > Commissioning > Settings ... or
Main menu > Settings > Data acquisition > Meter 1 (or 2 , 3 or 4 )
Operating line
Meter reading 1*
* Or meter reading 2, 3 or 4
11.3.8 Fault handling
Battery-powered and mechanical meters also continue to operate in the event of a
power failure. If power supply to the RMK770 controller fails, the pulses are not
counted.
When the Extra configuration menu is quit, a restart is made. Pulses received between
last storage and restart (maximum 5 minutes) are not counted.
No.
Text
9401
No pulse signal meter 1
9402
No pulse signal meter 2
9403
No pulse signal meter 3
9404
No pulse signal meter 4
Boiler sequence controller RMK770
11 Data acquisition
Range
Max. 20 characters
Effect
Meter input 1 receives no pulses from the
heat meter. Nonurgent message; must be
acknowledged
Meter input 2 receives no pulses from the
heat meter. Nonurgent message; must be
acknowledged
Meter input 3 receives no pulses from the
heat meter. Nonurgent message; must be
acknowledged
Meter input 4 receives no pulses from the
heat meter. Nonurgent message; must be
acknowledged
Factory setting
Meter reading 1*
189/232
CE1P3132en
23.04.2009