Siemens Synco 700 Series Basic Documentation page 200

Modular boiler sequence controller including extension modules rmz785, rmz787, rmz788 and rmz789
Hide thumbs Also See for Synco 700 Series:
Table of Contents

Advertisement

Fault text
Fault status
signal delay
Fault effect
Fault status messages
200/232
Building Technologies
HVAC Products
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Inputs > RMK770.D... (or RMZ78... )
Operating line
Normal position
Following can be set for each fault status message:
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Faults > Fault input 1 (or 2 , 3 or 4 )
Operating line
Fault text
Fault status signal delay
Fault acknowledgement
Fault priority
Impact of fault
Limit value fault on
Limit value fault off
* Or fault input 2, 3 or 4
** Depending on the "Input identifier"
These settings can be made only if the relevant input has previously been activated in
the extra configuration.
For more detailed information, refer to section 13.5 "Fault properties".
The text for the universal fault inputs is predefined via [Fault input 1]Fault through
[Fault input 4]Fault . The texts can be adapted.
Signal at the
fault input
Fault status
message
The fault status signal delay is used to set the period of time a fault must be pending to
be handled as such.
When parameterized "Stop" at the universal fault inputs, the controller switches off all
function blocks (boiler sequence manager, all boilers, primary controller, and the heat-
ing circuit). Frost protection continues to be active.
Number
Text
9000
>1 fault input fault
9001
[Fault input 1] fault *
9002
[Fault input 2] fault *
9003
[Fault input 3] fault *
9004
[Fault input 4] fault *
* Factory setting; text is editable
Boiler Sequence Controller RMK770
13 Function block "Faults"
Range
Open / Closed
Range
Max. 20 characters
00.00...59.55 m.s
None / Acknowledge /
Acknowledge and reset
Urgent / Nonurgent
No stop / Stop
0 / 1**
0 / 1**
Signal delay
Effect
Urgent message; must not be acknowl-
edged (effect at each fault input can be
selected)
Effect according to settings
Effect according to settings
Effect according to settings
Effect according to settings
Factory setting
Open
Factory setting
[Fault input 1]
Fault*
00.05 m.s
None
Nonurgent
Stop
1
0
CE1P3132en
23.04.2009