Inputs
Outputs
Display of faults
Deleting faults
Building Technologies
HVAC Products
When making diagnostics or the wiring test, logic states are displayed. The input is
active when 1 appears on the display. If "Normal position open" is selected, this is the
case when the contact is closed; if "Normal position closed" is selected, this is the case
when the contact is open.
Main menu > Commissioning > Wiring test > Faults > Outputs
Operating line
Fault relay 1
Fault relay 2
13.14 Diagnostic choices
Main menu > Miscellaneous > Inputs
Operating line
Fault button external
Fault input 1
Fault input 2
Fault input 3
Fault input 4
Main menu > Miscellaneous > Outputs
Operating line
Fault relay 1
Fault relay 2
Main menu > Faults > Faults current
Operating line
Fault 1...
...fault 10
Main menu > Faults > Fault history
Operating line
Fault 1...
...fault 10
Main menu > Faults > Fault status message bus
Operating line
Fault status message bus
Main menu > Faults > Delete faults
Operating line
Fault history will be deleted
Boiler sequence controller RMK770
13 Function block "Faults"
Range
Off / On
Off / On
Range
0 / 1 (1 = active)
According to the configuration
According to the configuration
According to the configuration
According to the configuration
Range
Off / On
Off / On
Adjustable values / remarks
Adjustable values / remarks
Adjustable values / remarks
Adjustable values / remarks