Trend Function Settings - Siemens Synco 700 Series Basic Documentation

Modular boiler sequence controller including extension modules rmz785, rmz787, rmz788 and rmz789
Hide thumbs Also See for Synco 700 Series:
Table of Contents

Advertisement

Settings
Explanations relating
to the settings
Notes on the
extra channel
Display values
Building Technologies
HVAC Products
11.1.3

Trend function settings

Main menu > Settings > Data acquisition > Trend > Trend channel 1...4
Operating line
Trend channel 1...
Trend channel 4
Trend signal
Geographical zone
(apartment)
Geographical zone
(room)
Outside temperature
zone
Y-axis min
Y-axis max
Selection extra channel
A trend channel is activated by assigning a "Trend signal" to it.
Each trend channel can be assigned a plant-specific text with max. 20 characters via
operating line "Trend channel x".
The bus address of the room for which the room temperature is to be recorded can be
set via the "Geographical zone".
To acquire the outside temperature via bus, set the relevant "Outside temperature
zone".
The Y-axes can be scaled for each trend channel. Datapoints "Y-axis min" and "Y-axis
max" refer to the value display and must be set according to the expected signal range.
There is no trend display if the current values are outside the selected range!
A second trend channel can be shown via operating line "Selection extra channel". This
channel is displayed as a dotted line.
Only every second measured value is displayed for the extra channel; thus, the value to
be measured should be put on the main channel.
The Y-axis label only refers to the primary channel. The extra channel is displayed accord-
ing to its Y-axis settings. If the axes differ, a warning triangle appears next to the axis.
The trend channels can be called up via the following menu:
Main menu > Data acquisition > Trend channel 1...4
The trend channels are displayed with the text assigned to them.
When a trend channel is selected, the display immediately switches to the 24-hour
view. The select-and-push knob allows you to navigate between the different views.
Boiler sequence controller RMK770
11 Data acquisition
Adjustable values / remarks
Channel name
(editable text, max. 20 characters)
Assign trend signal:
---, room temperature via bus, outside temperature via
bus, N.X1...A9(3).X4
1...126
Relevant only if "Room temp via bus" is selected
1...63
Relevant only if "Room temp via bus" is selected
1...31
Relevant only for "Outside temp via bus"
Depending on selected type
Depending on selected type
Trend channel 1...Trend channel 4
185/232