Here, an outside sensor can be configured. That sensor can be used for both the
heating circuit and the boiler sequence manager.
Digital input for activating the "Special day" function.
Digital input for activating the "Holidays" function.
Here, 4 universal inputs for display purposes can be configured.
The unit of these inputs can be defined at menu item Input identifier.
Main menu > Commissioning > Extra configuration > Input identifier
Operating line
Display input 1
Display input 2
Display input 3
Display input 4
For resolution, type of sensor, etc., refer to subsection 3.4.7 "Configuration of the
universal inputs and outputs".
Main menu > Commissioning > Extra configuration > Miscellaneous > Outputs
Operating line
Outside temperature relay
* Here, the free outputs are available for selection
Main menu > Commissioning > Extra configuration > Miscellaneous > Business card
Operating line
Business card
For more detailed information, refer to chapter 12 "Function block "Miscellaneous"".
3.4.6

Faults

Main menu > Commissioning > Extra configuration > Faults > Inputs
Operating line
Fault button external
Fault input 1
Fault input 2
Fault input 3
Fault input 4
* Here, the free inputs are available for selection
Main menu > Commissioning > Extra configuration > Faults > Outputs
Operating line
Fault relay 1
Fault relay 2
* Here, the free outputs are available for selection
For more detailed information, refer to chapter 13 "Function block "Faults"".
3.4.7

Configuration of the universal inputs and outputs

The universal inputs can accept digital signals and passive or active analog signals.
The inputs are activated via the basic and the extra configuration. Together with the
activation, the unit is assigned to the relevant input. For this reason, setting the input
identifier is not required with the RMK770 (with the exception of the 4 universal inputs
for display purposes and the 4 fault inputs).
Boiler Sequence Controller RMK770
3 Commissioning
Range
°C / % / g/kg / kJ/kg /
2
W/m
/ m/s / bar / mbar /
Pa / ppm / Universal
000.0 / Universal 0000 /
Digital
Range
RMK770..., RMZ7...*
Range
No / Yes
Range
RMK770..., RMZ7...*
Range
RMK770..., RMZ7...*
Factory setting
°C
°C
°C
°C
Factory setting
Factory setting
Yes
Factory setting
---
---
---
---
---
Factory setting
CE1P3132en
23.04.2009