Room Temperature Setpoints; Settings - Siemens Synco 700 Series Basic Documentation

Modular boiler sequence controller including extension modules rmz785, rmz787, rmz788 and rmz789
Hide thumbs Also See for Synco 700 Series:
Table of Contents

Advertisement

Remote setpoint
adjuster
Display of inputs/setpoints
Building Technologies
HVAC Products
Priority Name
Presence and timer
/
button
Special day contact
Holidays contact
Calendar
Time switch
10.4

Room temperature setpoints

10.4.1 Settings

The setpoints for the 4 room operating modes can be preselected by the plant operator
via operation. The setting values limit one another.
Main menu > Heating circuit > Room setpoints
Main menu > Settings > Heating circuit > Room setpoints
Operating line
Comfort
Precomfort
Economy
Protection
The preselected setpoints of Comfort
±3 K on the QAW740 room unit.
It is possible to use a conventional room temperature setpoint adjuster (absolute or
relative). For more detailed information, refer to the 2 subsections below.
The 4 setpoints are readjusted according to the following rules:
• Parallel readjustment of Comfort and Precomfort setpoint
• When the Economy setpoint is reached, it is shifted along with the Precomfort setpoint
• With the Protection setpoint, the Comfort, Precomfort and Economy setpoints are
limited
The effective setpoint is displayed on the service level and on the Info page.
Main menu > Heating circuit > Inputs/setpoints
Operating line
Current room temp setpoint
Room setpoint absolute*
Room setpoint relative*
* Only if configured via extra configuration
Boiler sequence controller RMK770
10 Heating circuit control
Explanation
The current time program can be overridden by
presence button
or timer button
The timer button at digital input
party KNX device) can also override the room
operating mode.
If 2 or more functions are triggered, the function
activated last prevails.
The current 24-hour program gets overridden by
the special day contact. The special day program is
activated in the time switch
The current 7-day program is overridden by the
holidays contact. The room operating mode can be
selected
If a special day is active, the associated 24-hour
program of the time switch is activated. Holidays, if
entered, are overridden. If holiday mode is active,
the selected room operating mode is used
In the time switch, the associated 24-hour program
is activated in accordance with the current week-
day. The 24-hour program forwards the current
room operating mode, the next setpoint, and the
time up to the next switching point
Range
19...35 °C
16...21 °C
10...19 °C
1...16 °C
and Precomfort mode can be readjusted by
Range
...°C
...°C
...°C
.
(or of a third-
Factory setting
21 °C
19 °C
16 °C
10 °C
Factory setting
159/232
CE1P3132en
23.04.2009