Supervision Of Faults - Siemens Synco 700 Series Basic Documentation

Modular boiler sequence controller including extension modules rmz785, rmz787, rmz788 and rmz789
Hide thumbs Also See for Synco 700 Series:
Table of Contents

Advertisement

Supervision of
main pump
Fault status messages
Fault supervision of
boiler sequence
Building Technologies
HVAC Products
6.4

Supervision of faults

The main pump (main twin pump) can be monitored with an overload input each and/or
a flow switch each (... Extra configuration > Boiler sequence manager > Inputs).
The parameters for the pump or twin pump fault inputs are fixed and cannot be
changed.
The fault status signal delay for the flow switch is 60 seconds.
The setting parameters for the main twin pump can be found on menu ... Settings > Boiler
sequence manager > Twin pump. For more detailed information about the functionality of
the twin pump, refer to chapter 5 "General functions, fundamentals".
Number
Text
2491
[Main pump] overload
2492
[Main pump B] overload
2493
[Main pump] no flow
[Main pump B] no flow
2494
2495
[Main pump] fault
For fault supervision of the boiler sequence, there are 3 binary fault inputs available.
These are freely configurable, whereby the 3 fault outputs use the following factory
settings:
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Boiler sequence manager > Fault settings > Fault input 1
Operating line
Fault text
Impact of fault
Fault acknowledgement
Fault priority
Fault status signal delay
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Boiler sequence manager > Fault settings > Fault input 2
Operating line
Fault text
Impact of fault
Fault acknowledgement
Fault priority
Fault status signal delay
Boiler sequence controller RMK770
6 Boiler sequence management
Effect
Nonurgent message; acknowledgement can
be parameterized; factory setting: "Acknowl-
edge"
Nonurgent message; acknowledgement can
be parameterized; factory setting: "Acknowl-
edge"
Nonurgent message; must be acknowledged
and reset
Nonurgent message; must be acknowledged
and reset
Urgent message; , must not be acknowl-
edged, plant stop
Range
A...Z
Stop / No stop
None / Acknowledge /
Acknowledge and reset
Urgent / Nonurgent
00.00...59.55 m.s
(minutes.seconds)
Range
A...Z
Stop / No stop
None / Acknowledge /
Acknowledge and reset
Urgent / Nonurgent
00.00...59.55 m.s
Factory setting
Water shortage
Stop
Acknowledge
Urgent
00.05 m.s
Factory setting
Overpressure
Stop
Acknowledge
Urgent
00.05 m.s
89/232
CE1P3132en
23.04.2009