Releasing and locking a boiler

A boiler can be released or locked either via the digital input (release input) or operation
(boiler operating mode).
Main menu > Commissioning > Settings > ... or
Main menu > Boiler > Boiler operating mode
Operating line
Preselection
With the digital release input, the boiler will stay locked as long as the input is passive.
If the boiler is locked via the release input, setting Frost prot (release input off) can be
used to select whether or not the boiler shall remain off also when there is a heat
request due to frost protection.
• Setting Off: The boiler also remains off in the event of risk of frost
• Setting On: The boiler will be put into operation to ensure protection against frost
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Boiler > Limitations
Operating line
Frost prot (release input off)
The boiler can also be locked depending on the outside temperature:
• The boiler will be locked when the attenuated outside temperature exceeds the
selected limit value
• The boiler will be released again when the composite outside temperature drops
1 K below the limit value
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Boiler > Operation settings
Operating line
Outside temp lock limit value
6.5

Test mode and commissioning aids

For commissioning and for test purposes, the boiler along with the burner can be put
into various operating states via the service level.
Main menu > Boiler > Test mode
Operating line
Preselection test mode
Boil setp test mode
Modulation value test mode
Actual value boiler temperature
The test mode is not automatically ended (no supervision of time-out!).
The inputs should only be overridden by qualified staff and only for a limited period of
time!
Modular Heating Controller RMH760B
6 Boiler temperature control
Range
Auto / Release DHW /
Off
Range
Off / On
Range
---- / 5...30 °C
Range
Auto /
Boiler off /
Pump on (burner off) /
Stage 1 controlled /
St 1+2 controlled /
Modulating fixed
10...95 °C
0...100 %
Measured value
Factory setting
Auto
Factory setting
On
Factory setting
---- °C
Factory setting
Auto
60 °C
0 %
CE1P3133en