Analog Fault Input With Limit Value Supervision - Siemens Synco 700 Series Basic Documentation

Modular boiler sequence controller including extension modules rmz785, rmz787, rmz788 and rmz789
Hide thumbs Also See for Synco 700 Series:
Table of Contents

Advertisement

>1 fault input fault
Fault handling
Example
Example
Building Technologies
HVAC Products
The fault with the highest priority is sent via KNX bus. If more than 1 fault input with
priority "Urgent" want to signal a fault, message ">1 fault input faulty" is delivered with
the highest priority. Without this fault status message, the message from only 1 fault
input would appear.
The digital status inputs cannot be monitored. We recommend to use wiring ensuring
that the signal drops out when a fault is pending.

13.8.2 Analog fault input with limit value supervision

An analog input can be monitored for limit value crossings.
An input that is already configured can also be monitored. For example, the main flow
temperature sensor can be monitored to ensure that the maximum flow temperature will
not be exceeded.
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Faults > Fault input ...
Operating line
Limit value fault on
Limit value fault off
* Depending on the input identifier (the example here applies to a digital input)
If "Limit value fault on" is greater than "Limit value fault off", the input is monitored for
overshoot.
Limit value fault on:
Limit value fault off:
If the temperature exceeds 80 °C, a fault is identified; if it drops again to a level below
75 °C, the fault is considered removed.
ON
OFF
ERROR
If "Limit value fault off" is greater than "Limit value fault on", the input is monitored for
undershoot.
Limit value fault on:
Limit value fault off:
If the temperature falls below 10 °C, a fault is identified; if it returns to a level above
12 °C, the fault is considered removed.
ON
OFF
ERROR
Boiler sequence controller RMK770
13 Function block "Faults"
Range
0 / 1*
0 / 1*
80 °C
75 °C
10 °C
12 °C
Factory setting
1
0
201/232
CE1P3132en
23.04.2009