Rectification Of Faults - Siemens Synco 700 Series Basic Documentation

Modular boiler sequence controller including extension modules rmz785, rmz787, rmz788 and rmz789
Hide thumbs Also See for Synco 700 Series:
Table of Contents

Advertisement

Building Technologies
HVAC Products
Number
Name (as supplied)
>1 boiler with address number 3
5532
5542
>1 boiler with address number 4
>1 boiler with address number 5
5552
5562
>1 boiler with address number 6
5591
Failure boiler sequence manager
5592
>1 boiler sequence manager
Number of boilers wrong setting
5593
Invalid lead boiler
5594
6001
>1 identical device address
7101
Fault extension module
7102
Fault extension module 2
7103
Fault extension module 3
9000
>1 fault input fault
9001
[Fault input 1] fault
9002
[Fault input 2] fault
9003
[Fault input 3] fault
9004
[Fault input 4] fault
9401
No pulse signal meter 1
9402
No pulse signal meter 2
9403
No pulse signal meter 3
9404
No pulse signal meter 4
15.2

Rectification of faults

Question
E.g., fault status message
"[HC 1] error flow sensor" ap-
pears although a sensor is
connected.
When commissioning the plant,
the wrong language was se-
lected.
How do I find the language I
need?
The device is completely
switched off, "Operation locked,
Remote operation" appears.
How do I start the device again?
The buttons on the QAW740
room unit do not work.
Boiler sequence controller RMK770
15 Fault tracing support
For explanation, refer to section ...
14.6
14.6
14.6
14.6
14.6
14.6
6.8
6.8
14.6
3.3.6
3.3.6
3.3.6
13.8.1
13.8.1
13.8.1
13.8.1
13.8.1
11.3.8
11.3.8
11.3.8
11.3.8
Reply
Check to see if, in addition, fault "Fault extension
module" occurred. This fault can lead to the
display of subsequential faults.
1. Press the ESC button and the OK knob simul-
taneously.
2. Choose the password level and enter number
112 as the password (same as international
emergency call) and confirm by pressing the
OK knob. The language changes to English.
3. Select your language from the Settings > Device
> Language menu.
Remote operation (OCI700.1) set the device to
commissioning mode, which has locked local
operation.
If the device is not corrected restarted via remote
operation, it maintains this state. Locally, the
device can only be restarted by briefly discon-
necting the power supply.
The room operating mode on the controller is
overridden by a higher priority.
217/232
CE1P3132en
23.04.2009