Siemens Synco 700 Series Basic Documentation page 130

Modular boiler sequence controller including extension modules rmz785, rmz787, rmz788 and rmz789
Hide thumbs Also See for Synco 700 Series:
Table of Contents

Advertisement

Fault checkback signal
shutoff valve
Flue gas temperature
limit exceeded
130/232
Building Technologies
HVAC Products
Number
Text (as supplied)
2344
[Boiler 4] underpressure
2345
[Boiler 5] underpressure
2346
[Boiler 6] underpressure
Number
Text (as supplied)
[K1 valve] no checkback
2351
signal
[K2 valve] no checkback
2352
signal
[K3 valve] no checkback
2353
signal
2354
[K4 valve] no checkback
signal
2355
[K5 valve] no checkback
signal
2356
[K6 valve] no checkback
signal
Number
Text (as supplied)
2361
[K1] flue gas overtem-
perature
2362
[K2] flue gas overtem-
perature
2363
[K3] flue gas overtem-
perature
2364
[K4] flue gas overtem-
perature
2365
[K5] flue gas overtem-
perature
2366
[K6] flue gas overtem-
perature
Boiler Sequence Controller RMK770
7 Boiler control
Effect
Priority, effect and acknowledgement can be
parameterized.
Supply state: Urgent, boiler stop, must be
acknowledged
Priority, effect and acknowledgement can be
parameterized.
Supply state: Urgent, boiler stop, must be
acknowledged
Priority, effect and acknowledgement can be
parameterized.
Supply state: Urgent, boiler stop, must be
acknowledged
Effect
Urgent message; must be acknowledged
and reset. Aggregate stop boiler 1
Urgent message; must be acknowledged
and reset. Aggregate stop boiler 2
Urgent message; must be acknowledged
and reset. Aggregate stop boiler 3
Urgent message; must be acknowledged
and reset. Aggregate stop boiler 4
Urgent message; must be acknowledged
and reset. Aggregate stop boiler 5
Urgent message; must be acknowledged
and reset. Aggregate stop boiler 6
Effect
Priority and effect can be parameterized.
Supply state: Nonurgent, no boiler stop,
must be acknowledged and reset
Priority and effect can be parameterized.
Supply state: Nonurgent, no boiler stop,
must be acknowledged and reset
Priority and effect can be parameterized.
Supply state: Nonurgent, no boiler stop,
must be acknowledged and reset
Priority and effect can be parameterized.
Supply state: Nonurgent, no boiler stop,
must be acknowledged and reset
Priority and effect can be parameterized.
Supply state: Nonurgent, no boiler stop,
must be acknowledged and reset
Priority and effect can be parameterized.
Supply state: Nonurgent, no boiler stop,
must be acknowledged and reset
CE1P3132en
23.04.2009