Overflow Value; Setting And Resetting Meter Readings; Meter Readings - Siemens Synco 700 Series Basic Documentation

Modular boiler sequence controller including extension modules rmz785, rmz787, rmz788 and rmz789
Hide thumbs Also See for Synco 700 Series:
Table of Contents

Advertisement

Pulse valency
Setting and resetting

meter readings

Display values
188/232
Building Technologies
HVAC Products
Main menu > Commissioning > Settings or
Main menu > Settings > Data acquisition > Meter 1 (or 2, 3 or 4 )
Operating line
Pulse unit
Pulse valency numerator
Pulse valency denominator

11.3.4 Overflow value

The overflow value ensures that the displayed readings on the connected meter and on
the RMK770 controller are identical. The value at which the meter's display returns to 0
can be set.
Unit and decimal place depend on the unit and the format.
The overflow value can only be changed with the OCI700.1 service tool.
Main menu > Commissioning > Settings or
Main menu > Settings > Data acquisition > Meter 1 (or 2, 3 or 4)
Operating line
Overflow value

11.3.5 Setting and resetting meter readings

In case of deviations, service staff can adjust the pulse meter reading via datapoint
"Meter reading current". This value can only be changed with the OCI700.1 service tool.
Datapoint "Reset monthly values" allows for deleting the last 15 monthly values. The
current meter reading is retained.
Main menu > Commissioning > Settings or
Main menu > Settings > Data acquisition > Meter 1 (or 2 , 3 or 4 )
Operating line
Reset monthly values
11.3.6 Meter readings
Each meter shows:
• The current reading
• The reading per month and the date associated with the reading over the last 15
months
Main menu > Data acquisition > Meter 1 (or 2 , 3 or 4 )
Operating line
Meter reading current
Unit
[Readout 1] date
[Readout 1] meter reading
...
[Readout 15] date
[Readout 15] meter reading
The monthly values are always stored at midnight at the end of the month.
Using datapoint "Monthly values", the 15 monthly values can be reset or deleted on the
password level.
Boiler Sequence Controller RMK770
11 Data acquisition
Range
Wh / kWh / MWh / kJ /
MJ / GJ / ml / l / m3 /
Heat cost unit /
No unit / BTU
1...9999
1...9999
Range
0...999'999'999
Range
Yes / No
Remarks
0...999'999'999
According to the configured display format
Factory setting
kWh
1
1
Factory setting
99'999'999 kWh
Factory setting
No
CE1P3132en