9
Troubleshooting
9.1
Error codes
Tab.27
Error codes are displayed at three different levels
Code
Type
Warning
A00.00
(1)
H00.00
Blocking
(1)
E00.00
Lock out
(1)
(1) The first letter indicates the type of error.
Tab.28
Warning codes
Code
Display text
A00.32
TOutside Open
A00.33
TOutside Closed
A00.34
TOutside Missing
A00.42
WaterPressureMissing
7725106 - v.01 - 05062019
The boiler is fitted with an electronic regulation and control unit. The heart
of the control is a microprocessor, which controls and also protects the
boiler. In the event of an error, a corresponding code is displayed.
Description
The boiler continues to operate but the cause of the warning must be investigated. A
warning can change into a blocking or lock-out.
The boiler starts up again automatically when the cause of the blocking has been recti
fied. A blocking can become a lock-out.
The boiler starts up again only when the cause of the lock-out has been rectified and
reset manually.
The meaning of the code can be found in the various error code tables.
Important
The error code is needed to find the cause of the error quickly and
correctly and for any support from De Dietrich.
9.1.1
Warning
Description
Outside temperature sensor is either
removed or measures a temperature
below range
Outside temperature sensor is either
shorted or measures a temperature
above range
Outside temperature sensor was
expected but not detected
Water pressure sensor was
expected but not detected
Solution
Outdoor temperature sensor open:
Bad connection: check the wiring and connec
tors
Incorrectly fitted sensor: check that the sensor
has been correctly fitted
Sensor is not present.
Faulty sensor: replace the sensor
Outdoor temperature sensor short-circuited:
Bad connection: check the wiring and connec
tors
Incorrectly fitted sensor: check that the sensor
has been correctly fitted
Faulty sensor: replace the sensor
Outdoor sensor not detected:
Outdoor sensor is not connected: Connect the
sensor
Outdoor sensor is not connected correctly:
Connect the sensor correctly
Water pressure sensor not detected
Water pressure sensor is not connected: con
nect the sensor
Water pressure sensor is not connected cor
rectly: connect the sensor correctly
9 Troubleshooting
AMC Pro
45