8 Maintenance
Fig.135
Cleaning the siphon
2
1
38
AMC Pro
Tab.26
Values at part load for G30/G31 (butane/propane)
AMC Pro 45
AMC Pro 65
AMC Pro 90
AMC Pro 115
(1) Nominal value
Caution
The O
full load.
8.3.5
Cleaning the siphon
Danger
The siphon must always be sufficiently filled with water. This
prevents flue gases from entering the room.
1. Dismantle the siphon and clean it.
2. Fill the siphon up with water.
3. Fit the siphon.
3
AD-0000086-01
Checking/setting values for O
(butane/propane)
values at part load must be higher than the O
2
at part load for G30/G31
2
O
(%)
(1)
2
5,7
- 6,2
(1)
5,7
- 6,2
(1)
5,7
- 6,2
(1)
5,7
- 6,2
(1)
values at
2
7725106 - v.01 - 05062019