Adjusting Advanced Parameters - DeDietrich EVODENS PRO Amc 45 Service Manual

Control panel & high-efficiency wall-hung gas boiler
Table of Contents

Advertisement

Fig.70
Step 11
6.2

Adjusting advanced parameters

Fig.71
Step 2
Fig.72
Step 3
Fig.73
Step 4
Fig.74
Step 5
Fig.75
Step 6
Fig.76
Step 7
Fig.77
Step 8
Fig.78
Step 9
7725106 - v.01 - 05062019
11. Press the
For more information, see
List of parameters, page 26
MW-3000316-01
The advanced parameters at installer level may only be changed by a
qualified professional. Code
the parameters.
Important
First, select a device, control PCB or zone to view or amend a
setting.
Caution
Modification of the factory settings may impair operation of the
device, control PCB or zone.
1. Navigate to the Installer menu.
2. Press the
MW-3000312-01
3. Keep pressing the
MW-3000313-01
4. Press the
MW-3000314-01
5. Keep pressing the
zone is displayed.
MW-3000406-01
6. Press the
MW-3000407-01
7. Keep pressing the
Important
The text
the appliance, control PCB or zone are available.
MW-3000408-01
8. Press the
MW-3000407-01
9. Press the
MW-3000337-01

key multiple times to go back to the main display.
must be entered in order to change
key to open the menu.
key until the code
key to confirm opening the menu.
key until the required device, control PCB or
key to confirm the selection.
key until
can only appear if the advanced parameters for
key to confirm the selection.
or
key to modify the value.
6 Installer instructions
is displayed.
is displayed.
AMC Pro
19