8. Troubleshooting
8.1 Error codes
The boiler is fitted with an electronic regulation and
control unit. The heart of the control system is a
microprocessor, the Comfort Master
the boiler and also protects the boiler. If a fault is
detected anywhere in the boiler, the boiler locks out
and the display will show the fault code as follows:
In a red flashing display:
•
The symbol
•
The symbol
RESET
•
The fault code (for example E:01)
The meaning of the error codes is given in the error
table. To do this, proceed as follows:
Error
Description
code
Storage unit PSU
é:00
parameter not found
The safety parameters
é:01
are incorrect
Supply temperature
é:02
sensor short circuited
Supply temperature
é:03
sensor open circuit
Temperature of heat
exchanger too low
é:04
Exchanger temperature
é:05
too high
96
, which controls
©
Probable causes
• Bad connection
• Bad connection
• PSU defective
• Bad connection
• Sensor fault
• Sensor not or badly connected
• Bad connection
• Sensor fault
• Sensor not or badly connected
• Bad connection
• Sensor fault
• Sensor not or badly connected
• No circulation
MCA Pro 45/65/90/115
i
Note the error code displayed.
The fault code is important for correct and
fast tracing of the nature of the fault and for
obtaining support from your heating contractor.
•
Press the
button for 2 seconds. If the error
RESET
code continues to display, search for the cause in
the error table and apply the solution.
i
If the display does not show
, the boiler must be switched OFF and then
switched ON again after 10 seconds before the
fault can be reset.
Checking / solution
• Check the wiring
• Check the wiring
• Replace PSU
• Check the wiring
• Check that the sensors are operating correctly
• Check that the sensor has been correctly fitted
• Replace the sensor if necessary
• Check the wiring
• Check that the sensors are operating correctly
• Check that the sensor has been correctly fitted
• Replace the sensor if necessary
• Check the wiring
• Replace the sensor if necessary
• Vent the air in the heating system
• Check the circulation (direction, pump, valves)
• Check the water pressure
• Check that the sensors are operating correctly
• Check that the sensor has been correctly fitted
• Check the cleanliness of the heat exchanger
but rather
RESET
MCA-Pro ISM Rv.4.1 2/2017