Levelflex FMP56, FMP57 HART
Additional information
Endress+Hauser
Meaning of the options
• Cancel
No action
• To factory defaults
All parameters are reset to the order-code specific factory setting.
• To delivery settings
All parameters are reset to the delivery setting. The delivery setting may differ from the
factory default if customer specific settings have been ordered.
This option is only visible if customer specific settings have been ordered.
• Of customer settings
All customer parameters are reset to their factory setting. Service parameters, however,
remain unchanged.
• To transducer defaults
Every measurment-related parameter is reset to its factory setting. Service parameters
and communication-related parameters, however, remain unchanged.
• Restart device
The restart resets every parameter which is stored in the volatile memory (RAM) to the
factory setting (e.g. measured value data). The device configuration remains unchanged.
Operating menu
191