Mitsubishi Electric AE-200A Instruction Book page 56

Air conditioning control system
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

Item
Charge Parameters
WT07190X01
■ File name
(without connection to an AE-50 controller)
"ChargeParameter"_[yyyy]-[mm]-[dd]"A"[Indoor unit address]-[Time period (1–5)].csv
(with connection to one or more AE-50 controllers)
"ChargeParameter"_[yyyy]-[mm]-[dd]"A"[AE-50 No.
(1–5)].csv
*1 "AE1," "AE2," or "AE3"
Note: The date will appear in the format that has been set on the [Unit Info.] screen.
Note: Time periods 1 through 5 can only be set from TG-2000A. When shipped from the
factory, only Time period 1 is settable.
■ File output destination
(without connection to an AE-50 controller)
[Root folder of the USB memory]\[Serial No.]\"OperationalData"\"ChargeParameters"\[Date]
(with connection to one or more AE-50 controllers)
[Root folder of the USB memory]\[Serial No.]\"OperationalData"\"ChargeParameters"\
[AE-50 No.
]\[Date]
*1
*1 "AE1," "AE2," or "AE3"
Note: The date will appear in the format that has been set on the [Unit Info.] screen.
■ File format
Row
Item
1st
File Type
2nd
Data range
*1
Indoor unit
3rd
address
4th
Item
5th–
Data
*2*3*4*5
66th
*1 The date will appear in the format that has been set on the [Unit Info.] screen.
*2 The separator character and decimal point character selected on the Measurement screen
(accessible via the Web Browser for Initial Settings) will be used to the data.
*3 Each value is the cumulative value between the start date and the end date.
*4 The value will not appear if the data does not exist.
*5 Each file contains the data of up to 62 days.
■ File sample
201
12/19/2013-1/10/2014
Address 31
Date,SaveValue,ThermoTime,FanTime,SubHeaterTime
12/19/2013,1258,0,465,0
12/20/2013,1260,0,468,0
12/21/2013,1262,0,472,0
12/22/2013,1264,0,477,0
12/23/2013,1266,0,490,0
:
01/10/2014,2058,0,1013,0
56
Description
*1
][Indoor unit address]-[Time period
Format
201
Start date + "–" + End date
"Address" + M-NET address
"Date,SaveValue,ThermoTime,FanTime,SubHeaterTime"
Date
*1
, Capacity-save value (min), Thermo-ON time (min),
Fan operation time (min), Sub-heater-ON time (min)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ae-50aAe-50eAe-200eAe-50

Table of Contents