Figure 15: Connecting The Battery To The Ups; Table 7: Suggested Fuse And Circuit-Breaker Values - Gamatronic Centric 3X480 VAC Installation Manual

For the 120 kw and 240 kw models
Hide thumbs Also See for Centric 3X480 VAC:
Table of Contents

Advertisement

4.3.4.4
ASSEMBLING AND CONNECTING THE BATTERIES
Note: The Centric supports the use of standard lead-acid batteries, and also lithium-ion batteries. If you
plan to use lithium-ion batteries, consult with your Centric dealer to be sure that the battery setup
parameter values are appropriate for the batteries you will be using.
1.
It is recommended that the battery cabinet(s) be located as close to the UPS as is practical.
2.
Assemble the batteries within the battery cabinet.
3.
Figure 15 shows the recommended connection to the UPS, which includes two fuses inside of each
battery cabinet, one on the plus line and one on the minus line. The recommended fuse values for
one set of two cabinets of 20 x 12 Vdc each are shown in Figure 15, according to the output capacity
of the UPS.
4.
Figure 15 assumes that the battery fuses can be easily disconnected when desired.
5.
Measure the dc voltage at the main terminals of the battery cabinets. Verify that you obtain values of
at least 240 Vdc for each battery cabinet, or at least 480 Vdc across the main battery CB.
6.
Connect the battery set to the Centric's positive ("+") battery bus bar, negative ("–") battery bus bar,
and Neutral bus bar. Refer to Figure 15 and Table 7. Observe proper polarity!
7.
The fuses between the battery cabinets and the Centric (F1, F2, F3, and F4 in Figure 15 must be
FAST FUSES (SEMICONDUCTOR FUSES); for example, the Ferraz Shawmut A70QS fuse.
8.
For initial startup to take place the battery must be connected to the UPS and available.
Note: Fuse values in Table 7 are for fuses F1 through F4 in Figure 15 and Figure 16, and are
based on 10-minute backup time at full load. If longer backup time is needed, please
consult with your dealer.
UPS capacity (kW)
Max. current (A)
Fast fuse (A)
Circuit breaker (A)
24
G
AMATRONIC

Figure 15: Connecting the battery to the UPS

Table 7: Suggested fuse and circuit-breaker values

30
60
80
160
60
125
63-125
125-180
200-250
E
I
L
LECTRONIC
NDUSTRIES
90
120
150
240
320
400
200
250
300
300-350
350-450
Centric 3x480 Vac, Installation Guide, rel. 2.2
.
TD
180
210
480
560
400
450
450-525
500-600
240
620
500
550-650