Device communication via the BMS bus
9.1.6 Alarm and operating messages via the BMS bus
Messages are transmitted to a maximum of 12 BMS channels. All alarm and operating
messages that may occur are described below.
9.1.6.1
Alarm messages
Message
Channel
Insulation resistance "prewarning"
Alarm 1 (insulation fault)
1
(Value < response value 1, R
Insulation resistance "alarm"
Alarm 2 (insulation fault)
2
(Value < response value 2, R
Connection system
4
Connection fault system
Connection PE
5
Connection fault earth
Device error
7
Internal device error
Start
insulation fault location
9
The insulation fault location is started
(only iso1685DP)
Overtemperature
10
Overtemperature coupling terminal L1/+
coupling
Overtemperature
11
Overtemperature coupling terminal L2/–
coupling
Overtemperature PGH
12
Overtemperature of the locating current injector
(only iso1685DP)
44
Description
< R
)
F
an1
< R
)
F
an2
Device communication via the BMS bus
9.1.6.2
Operating messages
Message
Channel
Current insulation resistance RF
Insulation resistance
1
(when R
Current insulation resistance RF
Insulation resistance
2
(when R
Leakage capacitance C
Leakage capacitance
4
Current system voltage U
Mains voltage
5
Partial voltage U+/PE
6
Current partial voltage terminal L1/+ to earth
Partial voltage U-/PE
7
Current partial voltage terminal L2/– to earth
PGH current
Current PGH locating current (when the EDS system is
8
(only iso1685DP)
active)
Temperature coupling
10
Current temperature of the coupling L1/+
Temperature coupling
11
Current temperature of the coupling L2/–
Temperature PGH
12
Current temperature of the locating current injector
(only iso1685DP)
9.1.6.3
Resetting error messages
Recorded errors are provided as alarm messages on the BMS bus.
The fault messages are reset via the device menu. If the error continues to exist, the mes-
sage will be generated again. The error can also be reset by means of the acknowledge-
ment command via the BMS bus.
Description
> (R
+ hysteresis))
F
an1
> (R
+ hysteresis))
F
an2
in nF, μF
e
N
isoxx1685Dx-x25_D00272_05_M_XXEN/04.2018

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ISOMETER iso1685DP-425 and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Isometer isohv1685d-425Isometer isolr1685dp-325

Table of Contents