Advertisement

Hardware description
3.5 MCI-PN board for SIMOTION P350-3
3.5.2

Display elements of the MCI-PN board

LED displays
The PROFINET interface with the four ports provides integrated LEDs used to display the
link and the activity. The front panel of the board has two LEDs (Fault and Sync) which
indicate the status.
Table 3- 10
Name
Link port (4x) Green On
Activity port
(4x)
Fault
Sync
1)
2)
54
Meaning of the LED displays
Color
Status
Yello
On
w
Red
Off
Flashing
(2 Hz)
Green
Off
1)
On
Flashing
(2 Hz)
Flashing
(0.5 Hz)
If no PROFINET IO with IRT has been configured, there will generally be no synchronization with
the send cycle.
Minimum flashing duration 3 s
Meaning
A device is connected to port x and a physical connection exists.
Data is being received or sent at Port x.
MCI-PN board is running correctly, data exchange with all
configured I/O devices is running.
Bus fault
2)
Failure of a connected I/O device
At least one of the assigned I/O devices cannot be addressed
Incorrect or no configuration
The SIMOTION P task system is not synchronized with the send
cycle of PROFINET IO. An internal substitute cycle of the same
size as the send cycle will be generated.
If no PROFINET IO has been configured, then generally no
synchronization will be made to the send cycle.
The SIMOTION P task system has synchronized with the send
cycle of PROFINET IO and data exchange is running.
The IsoPROFIBUS board (PROFIBUS) is synchronized to the
send cycle of PROFINET IO.
The SIMOTION P task system has synchronized with the send
cycle of PROFINET IO and cyclic data exchange is running.
The IsoPROFIBUS board (PROFIBUS) is not yet synchronized to
the send cycle of PROFINET IO.
Firmware download in progress
SIMOTION P350-3 and Panels
Manual, 05/2009