Avaya S8700 Installing Manual page 101

Media server with media gateway
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

Model 507B sneak fuse panel
Figure notes
1
507B sneak current protector (price
element code: comcode
107435091
)
2
25-pair male connector (In)
(comcode 846300994)
Each column of sneak fuse panels requires approximately 8 inches (20 cm) of horizontal wall
space. Connector cables connect the network interface to the sneak fuse panel. Also, use 157B
connecting blocks equipped with SCP-110 protectors for sneak current protection.
NOTE:
Sneak current protectors with a rating of 350 mA at 600 V must be Underwriters
Laboratories, Inc. (UL) listed for United States installations and Canadian Safety
Association
CSA) certified for Canadian installations. The panel contains two 25-pair
(
connectors, fuse removal tool, and fifty 220029 Sneak Fuses (and 2 spares). Use the
SCP-110 protectors with 110-type hardware and on the 507B sneak fuse panel. The
SCP-110 protectors can be ordered separately and installed on the 157B connecting block.
Fifty protectors are required per block.
Install the 507B near the network interface or patch panels with locally obtained #12 x
1
3/4-inch screws (or equivalent).
Sneak
Current
Protector
507B
3
25-pair female connector (out)
(comcode 846300994)
4
220029 fuses (inside panel). Use a
small screwdriver to pry top cover off
October 2002
Cabling the G600 Media Gateways