Huawei RMS-SNMP01A User Manual page 75

Snmp card
Hide thumbs Also See for RMS-SNMP01A:
Table of Contents

Advertisement

RMS-SNMP01A SNMP Card
User Manual
Figure 9-1 Setting the SNMP card IP address on the RCCMD client and SSL encrypted
transmission mode
Step 2 On the SNMP card WebUI, choose Config > RCCMD, and set RCCMD shutdown to
Enabled. For details, see
Step 3 On the SNMP card WebUI, the SSL encryption is Enabled by default and does not need to be
set. If the RCCMD client is set to the unencrypted mode, you need to set the SSL encryption
to Disabled on the SNMP card WebUI.
Step 4 Configure events. If you set the job type to RCCMD Message under Inverter on, specify the
IP address and port of the RCCMD client. The port is 6003 by default. If you need to modify
the port, modify the port on the RCCMD client at the same time to keep them the same. Enter
the message to be sent and set the message sending mechanism. For example, set it to
Immediately, once.
Step 5 On the Monitoring > Control page, start the UPS, and the inverter mode will be triggered.
Send the message indicating that the inverter is on.
Step 6 On the RCCMD client, you can check the log in the upper left corner of the RCCMD client
page.
Step 7 For a single UPS, you do not need to set the ESN. For a parallel system, set the ESN of the
UPS in which the SNMP card is located on the page.
----End
Issue 08 (2020-01-09)
4.6.6
RCCMD.
Copyright © Huawei Technologies Co., Ltd.
9 Protecting the Server by Using the RCCMD Software
67